4 Communicating with the Recorder
4-2
TESLA LITE User Manual
D03283R01.10
4.2 IRIG-B Time Input
The recorder is equipped to handle modulated or unmodulated GPS satellite
time IRIG-B signals. The IRIG-B time signal is connected to the BNC connec-
tion on the back of the recorder. When the IRIG-B signal is provided to the re-
corder and is enabled in the settings through the user interface, the IRIG-B
functional LED comes on and the recorder clock is referenced to this signal.
No settings are required to differentiate between modulated or unmodulated
signals; this is automatically detected by the recorder.
You can enable or disable the IEEE 1344 extension in the terminal mode set-
tings
Utilities>Setup>Time
. The enabled mode receives the year from the
IRIG-B signal. Disable this setting, if the available IRIG-B signal has no year
extension.
4.3 Communicating with the Recorder (IED)
You can connect to the recorder to access its user interface and SCADA ser-
vices by:
• Front USB 2.0 interface (user interface)
• Front or rear copper or optical Ethernet network link (user interface and
SCADA)
• Direct serial link (user interface and SCADA)
• External or internal modem link (user interface only)
The recorder has a front panel USB Port (Port 450), two Ethernet Ports 401
(one front and one rear panel) and two rear serial ports (Port 404 and Port 405)
that provide direct access to its user interface and SCADA services.
Summary of Contents for tesla lite
Page 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 78: ......
Page 126: ......
Page 134: ......
Page 214: ......
Page 234: ......
Page 280: ......
Page 284: ......
Page 288: ......