8 Configuring the Recorder
D03283R01.10
TESLA LITE User Manual
8-41
Settings
Figure 8.22: Power Factor Function Configuration
Table 8.17: Power Factor Function Settings
Element
Identifies the group to which this channel belongs. The Element forms
the first part of the channel name. The Element is selected when the
channel is created and is fixed once assigned when you are working
in the Element Tree view.
Description
Optional field (12 characters). Provides an additional description of
the channel that forms part of the channel name. Use if Element
Name and channel Type do not sufficiently identify the channel.
(“Channel Grouping and Naming” on page 8-7).
PF Detector Index
Identifies the Power Factor funtion.You can select any available fun-
tion. If the only option is “undefined”, you have already used all availa-
ble channels.
Watts/Vars function
to monitor
Specifies which Watts/Vars channel to use as input. Must be previ-
ously defined.
Trigger Settings
Disable detector if
VA less than
Allows the trigger to be supervised by a minimum VA level. Can be set
in primary or secondary units.
Limit
Power factor trigger level. 0 to 1 in 0.001 increments.
Delay
Requires the element to be energized before an active state is deter-
mined. Settable from 1 to 10,000 seconds in 1 second increments.
Trigger Action
Enable
Enables or disables the associated trigger. A trigger can be disabled
without altering the rest of its settings.
Fault
Initiates a fault (high speed) recording when triggered.
Summary of Contents for tesla lite
Page 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 78: ......
Page 126: ......
Page 134: ......
Page 214: ......
Page 234: ......
Page 280: ......
Page 284: ......
Page 288: ......