2 Connection and Power Up
D03283R01.10
TESLA LITE User Manual
2-3
Startup
Sequence
Front Panel
LEDs
Table 2.1: Startup Sequence
On Power Up
Front panel Test Mode LED turns on to indicate the
presence of power
~15-20 seconds after Power Up
Test Mode LED goes off
~25-30 seconds after Power Up
Recorder Functional LED turns on.At this point you
can log into the recorder
Records Stored LED turns on if records are present
Table 2.2: Front Panel LEDs
Front Panel LED
Indications
Recorder
Functional
Normally active green LED that is turned on approximately 25-30 sec-
onds after power up, indicating the unit is functional. If an internal fault
is detected, the LED is turned off. The LED state corresponds directly
with the Failure Contact
IRIG-B
Functional
Green LED that is active when a valid external time synchronizing sig-
nal is detected on the IRIG-B port
Recorder
Triggered
Green LED that is active while the recorder is in the process of creat-
ing a record
Records Stored
Green LED that turns on when there are records stored in the
recorder’s memory. The LED will flash to indicate the Storage Alarm
limit has been reached if so configured
Test Mode
Normally inactive red LED that turns on immediately on power up and
goes of after the self-test has been completed (approximately 15-20
seconds)
Alarm
Normally inactive red LED that indicates a failure has been detected
by the software. The presence of the Alarm LED means much of the
system is functioning and can be accessed for diagnosis
Summary of Contents for tesla lite
Page 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 78: ......
Page 126: ......
Page 134: ......
Page 214: ......
Page 234: ......
Page 280: ......
Page 284: ......
Page 288: ......