
Appendix E DNP3 Device Profile
D03283R01.10
TESLA LITE User Manual
Appendix E-17
NOTES
1. Binary Outputs are scanned with 500 ms resolution.
2. Events are not supported for Binary Outputs (group 10), but most of Binary
Output points can be mapped to Binary Inputs (group 2) with full Event and Class
Data support. See TESLA Control Panel /DNP Configuration/Point Map screen
for complete point lists and configuration options.
3. Binary Output data points are user selectable; the data points available in the
device for any given Binary Output point selection can be obtained through the
TESLA Control Panel software (see SCADA Setting Summary).
Supported Control Operations
Default Class
Assigned to Events
(1, 2, 3 or none)
Point
In
de
x
Name
Se
lec
t/Opera
te
D
ire
ct
Ope
rat
e
Direc
t Opera
te
- No Ack
Puls
e
On / NUL
Puls
e Of
f
Lat
ch
On / NUL
Lat
ch
Of
f /
NUL
Tr
ip
Clos
e
Count
>
1
Canc
el Curre
ntly Running O
p
eration
Name for
State when
value is 0
Name for
State when
value is 1
Change
Command Description
0
Output contact 1
-
-
-
-
-
-
-
-
-
-
-
Open
Closed
None
None
1
Output contact 2
-
-
-
-
-
-
-
-
-
-
-
Open
Closed
None
None
2
Output contact 3
-
-
-
-
-
-
-
-
-
-
-
Open
Closed
None
None
3
Output contact 4
-
-
-
-
-
-
-
-
-
-
-
Open
Closed
None
None
4
Output contact 5
-
-
-
-
-
-
-
-
-
-
-
Open
Closed
None
None
5
Output contact 6
-
-
-
-
-
-
-
-
-
-
-
Open
Closed
None
None
6
Retrieve Next Fault
Information Event
for Fault Locator 1
Y
Y
Y
Y
-
Y
Y
-
-
-
-
Inactive
Active
None
None
Pulse duration fixed
at 1
7
Retrieve Next Fault
Information Event
for Fault Locator 2
Y
Y
Y
Y
-
Y
Y
-
-
-
-
Inactive
Active
None
None
Pulse duration fixed
at 1
8
Retrieve Next Fault
Information Event
for Fault Locator 3
Y
Y
Y
Y
-
Y
Y
-
-
-
-
Inactive
Active
None
None
Pulse duration fixed
at 1
9
Retrieve Next Fault
Information Event
for Fault Locator 4
Y
Y
Y
Y
-
Y
Y
-
-
-
-
Inactive
Active
None
None
Pulse duration fixed
at 1
10
Retrieve Next Fault
Information Event
for Fault Locator 5
Y
Y
Y
Y
-
Y
Y
-
-
-
-
Inactive
Active
None
None
Pulse duration fixed
at 1
Summary of Contents for tesla lite
Page 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 78: ......
Page 126: ......
Page 134: ......
Page 214: ......
Page 234: ......
Page 280: ......
Page 284: ......
Page 288: ......