Appendix E DNP3 Device Profile
Appendix E-28
TESLA LITE User Manual
D03283R01.10
Implementation
Table
The following implementation table identifies which object groups and varia-
tions, function codes and qualifiers the device supports in both requests and re-
sponses. The Request columns identify all requests that are parsed by an
Outstation. The Response columns identify all responses that may be sent by
an Outstation.
NOTES
The implementation table lists all functionality required by the device (Outsta-
tion) as defined within the DNP3 IED Conformance Test Procedures. Any func-
tionality beyond the highest subset level supported is indicated by highlighted
rows. Any Object Groups not provided by an outstation are indicated by strike-
through (note these Object Groups will still be parsed).
DNP Object Group & Variation
Request
Outstation parses
Response
Outstation can issue
Group
Num
Var
Num
Description
Function Codes
(dec)
Qualifier Codes (hex)
Function Codes
(dec)
Qualifier Codes (hex)
1
0
Binary Input - Any Variation
1 (read)
06 (no range, or all)
129 (response)
00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
1
1
Binary Input - Packed format
1 (read)
06 (no range, or all)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
1
2
Binary Input - With flags
1 (read)
06 (no range, or all)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
2
0
Binary Input Event - Any Variation
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
17, 28 (index)
2
1
Binary Input Event - Without time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
2
2
Binary Input Event - With absolute
time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
2
3
Binary Input Event - With relative
time
1 (read)
06 (no range, or all)
07, 08 (limited qty)
129 (response)
130 (unsol. resp)
17, 28 (index)
10
0
Binary Output - Any Variation
1 (read)
06 (no range, or all)
129 (response)
00, 01 (start-stop)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
10
2
Binary Output - Output Status with
flag
1 (read)
06 (no range, or all)
00, 01 (start-stop)
07, 08 (limited qty)
17, 28 (index)
129 (response)
00, 01 (start-stop)
12
1
Binary Command - Control relay
output block (CROB)
3 (select)
4 (operate)
5 (direct op)
6 (dir. op, no ack)
17, 28 (index)
129 (response)
Echo of request
20
0
Counter - Any Variation
1 (read)
7 (freeze)
8 ( freeze noack)
9 (freeze clear)
10 (frz. cl. noack)
06 (no range, or all)
129 (response)
Summary of Contents for tesla lite
Page 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 78: ......
Page 126: ......
Page 134: ......
Page 214: ......
Page 234: ......
Page 280: ......
Page 284: ......
Page 288: ......