8 Configuring the Recorder
D03283R01.10
TESLA LITE User Manual
8-29
Maximum Change
Specifies the maximum impedance change to be detected.
Definite Delay
Requires the element to be energized before an active state is deter-
mined. Settable from 0 to 1,200 seconds in half-cycle increments.
Trigger Actions
Enable
Enables or disables the associated trigger. A trigger can be disabled
without altering the rest of its settings.
Fault
Initiates a fault (high speed) recording when triggered.
Swing
Initiates a swing (low speed) recording when triggered.
If both Fault and Swing are enabled, the recorder will attempt to cre-
ate a combined record.
Log
Logs a message in the Event Log when triggered.
Notify
Contacts the RecordBase Central Station when triggered. Can be
used to initiate wide area swing recordings and/or automated record
transfer (“Notify” on page 7-13)
Cross Trigger
Activates the cross-trigger contact (#6) to trigger another device.
Priority
Specifies the priority to be assigned to records created by this trigger.
The priority is used to determine Central Station notification.
1 - 3 (3 is the highest priority). (“Notify” on page 7-13).
Alarm Contact
Specifies a rear panel contact to be closed when triggered. Contacts
are closed momentarily for one second. Contact assignment is not
exclusive, allowing multiple triggers to activate the same contact.
Contacts assigned for storage alarms (“TESLA Alarms” on page 8-6)
will not be available for use here.
Table 8.12: Impedance Channel Settings
Summary of Contents for tesla lite
Page 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 78: ......
Page 126: ......
Page 134: ......
Page 214: ......
Page 234: ......
Page 280: ......
Page 284: ......
Page 288: ......