Appendix D Modbus Functions
Appendix D-10
TESLA LITE User Manual
D03283R01.10
• The TESLA LITE IED model number is 4001.
• Version and issue will each be positive integers, say X and Y.
• The TESLA LITE is defined as “Model 4001, Version X Issue Y”
Preset Single Register (Function Code 06)
Channel
Address
Value
Scaled Up By
Event Information (See
Accessing TESLA Event Infor-
mation, below)
42099 – 42051
Refresh event list
42049
No data required
N/A
Acknowledge the current event and get the next event
42050
No data required
N/A
Get the next event (without acknowledge)
42051
No data required
N/A
Diagnostic Subfunctions (Function Code 08)
Return Query Data (Subfunction 00)
This provides an echo of the submitted message.
Restart Comm. Option (Subfunction 01)
This restarts the Modbus communications process.
Force Listen Only Mode (Subfunction 04)
No response is returned. IED enters “Listen Only” mode. This
mode can only be exited by the “Restart Comm. Option” com-
mand.
Report Slave ID (Function Code 17/0x11)
A fixed response is returned by the IED, including system model, version and issue numbers.
Channel
Type
Bytes
Value
Model Number
Read Only
0 and 1
0x07D00 = 2000 decimal
Version Number
Read Only
2 and 3
Version number
Issue Number
Read Only
4 and 5
Issue number
Summary of Contents for tesla lite
Page 1: ...TESLA LITE Power System Recorder User Manual Version 1 1 Rev 0 ...
Page 2: ......
Page 4: ......
Page 6: ......
Page 10: ......
Page 12: ......
Page 20: ......
Page 24: ......
Page 78: ......
Page 126: ......
Page 134: ......
Page 214: ......
Page 234: ......
Page 280: ......
Page 284: ......
Page 288: ......