900-00277-01-001 Rev A
55
Mojave ESS Battery
The Mojave ESS battery is sold for use with the Mojave inverter. It is a nominal 48-volt lithium-ion
system intended for use in non-dwelling spaces. The battery can be charged and discharged at up
to 200 Adc continuously.
This battery incorporates passive overcurrent protection in the form of circuit breakers and fuses.
The battery incorporates active BMS protection for overcurrent, overvoltage, over-discharge, and
over-temperature conditions. The battery communicates operating limits to the connected inverter
via CAN communications. It self-protects in case these limits are violated.
WARNING: Explosion, Electrocution, or Fire Hazard
A battery can present a risk of electric shock, burns from high short-circuit current, fire,
or explosion. Observe proper precautions.
Ensure the cables are properly sized.
Ensure clearance requirements are strictly enforced around the batteries.
Ensure the area around the batteries is well ventilated and clean of debris.
Never smoke near the batteries. Never allow a spark or flame near the batteries.
Always use insulated tools. Avoid dropping tools onto batteries or other electrical parts.
Never charge a frozen battery.
If the battery must be removed, always remove the grounded terminal from the battery
first. Make sure all devices are de-energized or disconnected to avoid causing a spark.
CAUTION: Equipment Damage
Failure to install or use this product as instructed can result in damage to the product
that may not be covered under the limited warranty.
This product has no user-replaceable parts. It is only serviceable by qualified
personnel.
Do not connect multiple Mojave ESS batteries in series or in parallel. Do not connect
them to other batteries.
IMPORTANT:
See page 8 for labels displayed on the battery.
Install this product in accordance with local electrical, building, fire, and other codes or
utility requirements.
Use with copper conductors rated 75°C minimum.
When installing batteries, leave adequate clearance between batteries.
If installed in the United States, all wiring methods shall be in accordance with the
National Electrical Code® (NFPA 70), Current Edition.
If installed in Canada, all wiring methods shall be in accordance with the Canadian
Electrical Code®, C22.1, Current Edition.
Wear complete eye and clothing protection when working with batteries.
Do not expose to rain or spray.
Fire suppression equipment must be available in case of fire. The minimum required
equipment for this installation is a type ABC fire extinguisher.
NOTE:
The
exterior
covers have been removed from the battery due to the risk of damage in
transport. These covers should not be attached until the rest of the installation process
is complete.
The battery housing is still protected by a set of inner covers. One of these covers must
be removed for wiring purposes. See page 59.