Operation
Wiring
WARNING: Shock Hazard
This battery must be turned off (using the circuit breaker) for at least 30 seconds before
opening the wiring compartment.
Figure 31 Removing Wiring Cover
Wiring Connections
The battery’s exterior
covers are not installed before shipping. The interior covers are present. The
topmost of these must be removed for wiring access.
To open the wiring compartment, use a 5 mm hex (Allen) driver to remove the four M6 screws
holding the cover in place (
G
in Figure 31).
The following items are included in the hardware kit:
Exterior
covers
Communication cable, CAT5E, length/max length
2 primary conductors, 4/0 AWG, red and black
Grounding conductor, #4 AWG
Wiring to Inverter
Although battery conductors are provided: If it is necessary to substitute longer cables, they must
meet the following requirements:
Size: 4/0 AWG
Maximum length: 10’ (3 m)
Temperature rating: 75°C
Termination: 8 mm ring lug