Operation
Installation
Requirements
Make certain to observe all environmental and placement requirements for this product.
Indoor installation only, with an operating temperature range of 0 to 45°C. Installers should check with
local authorities to confirm maximum permitted installation size or any other requirements.
This product is to be installed on the floor. The battery must be anchored against a wall or similar
surface. The back of the product will not be accessible after installation.
Install this product in a dry area free of moisture and condensation. Do not install in an area where
flooding may occur. If the water level rises above ¼” or water is sprayed on the product, stop using the
product immediately.
This product must be used in a negative-ground system, with the negative conductor mechanically
bonded to the system ground.
TL 797 or UL 797A conduit of 1½” size must be installed between inverter and battery bank.
This product is not meant for installation in hazardous locations where concentrations of gas may
accumulate and ignite.
Alarms for smoke, heat, and/or flammable gas must be installed on the site, in accordance with building,
fire, and installation codes.
Ventilation:
Room must not be sealed; airflow to the outside is required
Use of an exhaust fan is recommended
Keep the following away from this product:
Water
Moisture
Dust, particularly conductive material
NOTE: To meet UL 9540 in certain jurisdictions:
A Mojave ESS battery should not be installed within 3' (1 m) of a doorway, window, or
another battery.
A maximum of 2 units may be installed in an attached non-living space (a garage or
similar structure). Living spaces include bathrooms, toilet rooms, closets, halls, and
storage spaces.
A maximum of 5 units may be installed in a location detached from a living space
(a shed, or similar structure more than 5' or 1.52 m from a house or dwelling)
Emergency Protection
Alarms for smoke, heat, and/or flammable gas must be installed on the site.
In case of emergency or uncontrolled operation, the battery is equipped with a 250 A circuit breaker.
When these conditions occur, open this breaker immediately.
In case of fire:
Small fire — A type ABC extinguisher is the minimum required safety equipment.
Large fire — Vacate the area and contact emergency services.
In case of gas leak, take the following steps to prevent gas accumulation:
Turn on ventilation fans
Open external windows
Close internal doors