20
900-00277-01-001 Rev A ©2021 OutBack Power. All Rights Reserved.
User Interface
Additional items under the
Generator
tab:
Power
— The power in watts (W) being imported from the generator.
Frequency
— The frequency in hertz (Hz) measured at the inverter’s L1 and L2
G
EN
terminals.
Voltage L1
and
Voltage L2
— The voltage in AC volts (Vac) measured at the inverter’s L1 and L2
G
EN
terminals.
Current L1
and
Current L2
— The current in AC amperes (Aac) measured at the inverter’s L1 and L2
G
EN
terminals.
AGS Status
Enabled
— The AGS function has been activated in the
Actions Menu
and also in
AGS
under the
Generator
tab. (See pages 22 and 46.) It is waiting for proper conditions to start the generator.
Disabled
— The AGS function has been been deactivated in the
Actions Menu,
in the
Generator
tab, or both. The generator may be started manually, but it will not start automatically.
Timer
— The timer that runs when the
Status
is
Warming Up
,
Connected
, or
Cooling Down
.
Info
— This item lists a series of messages providing additional information to system operation. AGS
conditions will appear here. A common message is
Gen going through warmup period
. If the
generator is not in use, this item will read
None
. When
Error
is present as a
Status
, the specific name of
the error (such as
At Minimum SOC setting
) will appear here
.
See the
EVENTS
view on page 24 and
Troubleshooting
on page 63 for more information on symptoms
and errors.