Electrical connection
Prosonic S FMU95 PROFIBUS DP
28
Hauser
Display
POWER
HART
0/4…20mA
Sync
Fuse
I
1
FDU-
Sensor
RD
1
1
BK
10
YE
9
40
39
5
4
6
7
8
1
Service
Relay
2
1
3
1
L
N
PE
2
90 … 253 VAC
10.5 … 32 VDC
3
4
A0035932
24
Connection of the power supply in the DIN rail housing
1
Metal DIN rail in cabinet
2
Terminal strip (no contact to DIN rail)
3
Protective ground terminal strip (with contact to DIN rail)
4
Grounding via DIN rail
6.3.2
Connection to a PROFIBUS DP network
For information on the layout of a PROFIBUS DP network, see Operating Instructions
BA00034S, "PROFIBUS DP/PA - Guidelines for planning and commissioning"
Cable specification
For transmission rates up to 12 Mbit/s, use cable type A according to EN 50170.
• Characteristic impedance: 135 to 165 Ω at a measuring frequency of 3 to 20 MHz
• Cable capacitance: < 30 pF/m
• Wire cross-section: > 0.34 mm
2
(22 AWG)
• Wires: twisted pairs, 1x2, 2x2 or 1x4 conductors
• Loop-resistance: 110 Ω/km
• Signal attenuation: < 9 dB over the entire length of the cable segment
• Shielding: copper braided shielding or braided shielding and foil shield
Pre-terminated cables are available from Hauser.
T-junction boxes
It is recommended to connect the Prosonic S using T-junction boxes.
Suitable junction boxes are available from Hauser.