Prosonic S FMU95 PROFIBUS DP
Installation
Hauser
19
Installation instructions
1.
2.
3.
4.
A0032561
15
Installation of the remote display and operating module
5.5
Mounting the sensors
Further information and the documentation currently available can be found on
the Hauser website:
www.endress.com
→ Downloads.
Sensor documentation:
• TI01469F (FDU90)
• TI01470F (FDU91)
• TI01471F (FDU91F)
• TI01472F (FDU92)
• TI01473F (FDU93)
• TI01474F (FDU95)
Sensors FDU80/80F/81/81F/82/83/84/85/86/96 can no longer be ordered. The
Prosonic S transmitter can still be connected if the sensors are already installed.
5.6
Post-installation check
Perform the following checks after mounting the device:
Is the device undamaged (visual inspection)?
Does the device match the measuring point specifications such as process temperature,
process pressure, ambient temperature, measuring range etc.?
If provided: are the measuring point number and labeling correct?
Is the measuring device adequately protected against precipitation and direct sunlight?
In the case of the field housing: are the cable glands tightened correctly?