Electrical connection
Prosonic S FMU95 PROFIBUS DP
34
Hauser
•
Resistance
Max. 8 Ω per wire
•
Capacitance, wire to shield
Max. 60 nF
•
Protective ground (for FDU91F/93/95)
May not be within the shielding.
Suitable connection cables are available from Hauser (→ 74).
6.3.5
Shortening the sensor cable
NOTICE
Damaged wires or no return conductor may cause malfunctions
‣
Do not damage the wires when removing the insulation.
‣
After shortening the cable, twist the shielding metal braiding and connect it to the "BK"
terminal.
‣
If the cable has a protective ground (GNYE), do
not
connect the protective ground to
the cable shield.