Electrical connection
Prosonic S FMU95 PROFIBUS DP
24
Hauser
6.2.4
Terminal assignment
Terminal type
Prosonic S has plug-in spring terminals. Rigid conductors or flexible conductors with
ferrules can be inserted directly into the terminal without using the lever, and create a
contact automatically.
Terminal areas
Address
T
erm.
DP
of
f
on
of
f
on
SW
HW
1
2
3
4
5
6
7
8
1
2
3
4
A(N)
66
B(P)
65
Display
POWER
Sync
Fuse
40
39
Service
3
2
1
1
1
10
9
1
FDU-Sensor
YE
BK
RD
14
13
12
2
YE
BK
RD
17
16
15
3
YE
BK
RD
20
19
18
4
YE
BK
RD
23
22
21
5
YE
BK
RD
26
25
24
6
YE
BK
RD
29
28
27
7
YE
BK
RD
32
31
30
8
YE
BK
RD
35
34
33
9
YE
BK
RD
38
37
36
10
YE
BK
RD
FDU-Sensor
A0035251
21
Terminal areas of Prosonic S FMU95
Terminals for power supply (AC version)
• Terminal 1: L (90 to 253 V
AC
)
• Terminal 2: N
• Terminal 3: potential equalization
• Fuse: 400 mA T
Terminals for power supply (DC version)
• Terminal 1: L+ (10.5 to 32 V
DC
)
• Terminal 2: L-
• Terminal 3: potential equalization
• Fuse: 2AT
Terminals for level inputs
In all device versions
• Sensor 1: terminals 9 (yellow), 10 (black), 11 (red)
• Sensor 2: terminals 12 (yellow), 13 (black), 14 (red)
• Sensor 3: terminals 15 (yellow), 16 (black), 17 (red)
• Sensor 4: terminals 18 (yellow), 19 (black), 20 (red)
• Sensor 5: terminals 21 (yellow), 22 (black), 23 (red)
In device versions with 10 sensor inputs
• Sensor 6: terminals 24 (yellow), 25 (black), 26 (red)
• Sensor 7: terminals 27 (yellow), 28 (black), 29 (red)
• Sensor 8: terminals 30 (yellow), 31 (black), 32 (red)
• Sensor 9: terminals 33 (yellow), 34 (black), 35 (red)
• Sensor 10: terminals 36 (yellow), 37 (black), 38 (red)