Commissioning
Prosonic S FMU95 PROFIBUS DP
50
Hauser
9.3.6
Parameter set "LVL N Linearisat."
0%
100%
0%
100%
100%
0%
100%
0%
0%
100%
A
B
C/D
E
F/G
H
H
A0021476
42
Types of linearization
A
None
B
Table
C
Pyramid bottom
D
Conical bottom
E
Angled bottom
F
Sphere
G
Horizontal cylindrical
H
Intermediate height
Navigation
Level → Level (LVL) N → Basic setup → LVL N Linearisat.
Parameter
•
Type
Select the type of linearization (see above)
•
Customer unit
Specify the unit for the linearized value.
•
Max. scale
Specify the maximum vessel content (100 %) in the selected customer unit.
Not displayed if
Type
=
Table
.
If
Type
=
Horizontal cyl.
or
Sphere
, the
Max. scale
must always refer to a completely
full tank.
•
Diameter
Only displayed if
Type
=
Horizontal cyl.
or
Sphere
.
Specify the diameter D of the tank.
•
Intermediate height (H)
Only displayed if
Type
=
Angled bottom
,
Pyramid bottom
or
Conical bottom
Specify the intermediate height H of the vessel (see above).