Prosonic S FMU95 PROFIBUS DP
Electrical connection
Hauser
33
Address
T
erm.
DP
of
f
on
of
f
on
SW
HW
1
2
3
4
5
6
7
8
1
2
3
4
A(N)
66
B(P)
65
1
1
10
9
1
FDU-Sensor
YE
BK
RD
14
13
12
2
YE
BK
RD
17
16
15
3
YE
BK
RD
20
19
18
4
YE
BK
RD
23
22
21
5
YE
BK
RD
26
25
24
6
YE
BK
RD
29
28
27
7
YE
BK
RD
32
31
30
8
YE
BK
RD
35
34
33
9
YE
BK
RD
38
37
36
10
YE
BK
RD
FDU-Sensor
GNYE
GNYE
Display
POWER
Sync
Fuse
40
39
Service
2
1
3
90 … 253 VAC
10.5 … 32 VDC
5
4
3
PE
PE PE
L
N
1
2
A0038736
28
Potential equalization of metallic sensors in DIN rail housing
1
FDU91F/93/95/96 (FDU83/84/85/86)
2
Metal DIN rail in cabinet
3
Grounding via DIN rail
4
Protective ground terminal strip (with contact to DIN rail)
5
Terminal strip (no contact to DIN rail)
6.3.4
Sensor extension cable
L
WARNING
Explosion Hazard
‣
Use a terminal box to connect the extension cable.
‣
If the terminal box is installed in hazardous areas, comply with applicable national
requirements.
Extension cable specifications
•
Maximum total length (sensor cable + extension cable)
300 m (984 ft)
•
Number of wires
As per connection diagram
•
Shielding
One shielding braid for the YE wire and one for the RD wire (no foil shield)
•
Cross-section
0.75 to 2.5 mm
2
(18 to 14 AWG)