Proline Prosonic Flow 90
6 Commissioning
Hauser
71
Performing a zero point adjustment
1.
Operate the system until normal operating conditions resume.
2.
Stop the flow (v = 0 m/s).
3.
Check the shut-off valves for leaks.
4.
Check that operating pressure is correct.
5.
Using the local display, select the “ZERO POINT ADJUSTMENT” function in the function
matrix:
HOME
→
F
→
R
→
PROCESS PARAMETER
PROCESS PARAMETER
→
F
→
R
→
ZERO POINT ADJ.
6.
When you press
OS
you are automatically prompted to enter the code if the function matrix
is still disabled. Enter the code.
7.
Use
OS
to select START and press
F
to confirm.
Select YES at the prompt and press
F
again to confirm. Zero point adjustment now starts.
– The message “ZEROPOINT ADJUST RUNNING” appears on the display for 30...60 seconds
while adjustment is in progress.
– If the fluid velocity in the pipe exceeds 0.1 m/s, the following error message appears on the
display: ZERO ADJUST NOT POSSIBLE.
– When the zero point adjustment is completed, the “ZERO ADJUST.” function reappears on
the display.
8.
Back to the HOME position
– Press and hold down the Esc key (
X
) for longer than three seconds.
– Repeatedly press and release the Esc key (
X
).
Summary of Contents for Prosonic Flow 90
Page 4: ...Brief operating instructions Proline Prosonic Flow 90 4 Endress Hauser...
Page 42: ...4 Wiring Proline Prosonic Flow 90 42 Endress Hauser...
Page 62: ...5 Operation Proline Prosonic Flow 90 62 Endress Hauser...
Page 74: ...7 Maintenance Proline Prosonic Flow 90 74 Endress Hauser...
Page 78: ...8 Accessories Proline Prosonic Flow 90 78 Endress Hauser...
Page 94: ...9 Trouble shooting Proline Prosonic Flow 90 94 Endress Hauser...
Page 108: ...10 Technical data Proline Prosonic Flow 90 108 Endress Hauser...
Page 112: ...Index Proline Prosonic Flow 90 112 Endress Hauser...
Page 114: ...www endress com worldwide BA068D 06 en 11 04 50099981 FM SGLM6 0...