Electrical connection
Deltabar FMD72
20
7.1.1
Screening with cable shield
Screening with cable shield is described in the associated documentation SD00354P. The
documentation is provided with the connecting cables.
7.2
Connecting the sensor module HP to the transmitter
!
WARNING
Is the supply voltage switched off?
Risk of electric shock and/or explosion!
►
Switch off the supply voltage before connecting the device.
• Screw on the housing cover of the terminal compartment of the sensor module HP.
• Guide the cable of the transmitter through the cable gland of the sensor module HP. Use the
shielded 4-wire cable that is provided. The wire ends are color-coded to match the corresponding
terminal.
• Connect device in accordance with the following diagram.
• Screw down housing cover.
6
5
5
7
2
3
4
3
4
1
2
1
6
5
NPT ½"
M20
8
8
A0017529
1
BK (black)
2
BU (blue)
3
WH (white)
4
BN (brown)
5
Sensor module HP
6
Transmitter
7
Ground terminal
8
Torque 0.4 Nm
7.2.1
Screening with cable shield
Screening with cable shield is described in the associated documentation SD00354P. The
documentation is provided with the connecting cables.
Summary of Contents for Deltabar FMD72
Page 2: ......
Page 107: ......
Page 108: ...www endress com worldwide 71191239 71191239 BA01044P 00 EN 02 12 71191239 CCS COSIMA...