Description of device parameters
Deltabar FMD72
86
Description
Select the linearization mode.
Options
• Linear
The level is output without being converted beforehand. "Level before Lin" is output.
• Erase table
The existing linearization table is deleted.
• Manual entry (sets the table to edit mode, an alarm is output):
The value pairs of the table (X-value (193/040) and Y-value (041)) are entered manually.
• Semi-automatic entry (sets the table to edit mode, an alarm is output):
The container is emptied or filled in stages in this entry mode. The device automatically records
the level value (X-value (193/040)). The associated volume, mass or % value is entered manually
(Y-value (041)).
• Activate table
The table entered is activated and checked with this option. The device shows the level after
linearization.
Factory setting
Linear
Unit after lin. (038)
Navigation
Setup
®
Advanced Setup
®
Linearization
®
Unit After Lin. (038)
Write permission
Operators/Service engineers/Expert
Description
Select volume unit, mass, height or % (unit of the Y-value).
Options
• %
• cm, dm, m, mm
• hl
• in
3
, ft
3
, m
3
,
• l
• in, ft
• kg, t
• lb
• gal
• Igal
Factory setting
%
Line number (039)
Navigation
Setup
®
Advanced Setup
®
Linearization
®
Line number (039)
Write permission
Operators/Service engineers/Expert
Description
Enter the number of the current point in the table. The subsequent entries in "X-value" and "Y-value"
refer to this point.
Input range
1...32