Deltabar FMD72
Description of device parameters
85
Navigation
Setup
®
Advanced Setup
®
Level
®
Full height (033)/(188)
Write permission
Operators/Service engineers/Expert
Description
Enter the height value for the upper calibration point (container full). The unit is selected via the
"Height unit" parameter.
Prerequisite
• "Level Selection" = "In height"
• "Calibration mode" = Dry -> entry
• "Calibration mode" = Wet -> display
Factory setting
URL is converted to a level unit
Adjust density (034)
Navigation
Setup
®
Advanced Setup
®
Level
®
Adjust Density (034)
Write permission
Operators/Service engineers/Expert
Description
Enter the density of the medium used to perform the calibration. The measured pressure is converted
to a height using the "Height unit" and "Adjust Density" parameters.
Factory setting
1,0
Process Density (035)
Navigation
Setup
®
Advanced Setup
®
Level
®
Process Density (035)
Write permission
Operators/Service engineers/Expert
Description
Enter a new density value for density correction. The calibration was carried out with the medium
water, for example. Now the container is to be used for another medium with another density. The
calibration is corrected appropriately by entering the new density value in the "Process Density"
parameter.
Note
If you change to dry calibration after completing a wet calibration using the "Calibration mode"
parameter, the density for the "Adjust Density" and "Process Density" parameters must be entered
correctly before changing the calibration mode.
Factory setting
1,0
Lin. mode (037)
Navigation
Setup
®
Advanced Setup
®
Linearization
®
Lin. Mode (037)
Write permission
Operators/Service engineers/Expert