Commissioning
Deltabar FMD72
50
The values entered for "Empty Calib./Full Calib.", "Set LRV/Set URV", and the applied pressure
values must be at least 1% apart. The value will be rejected, and a warning message displayed,
if the values are too close together. Further limit values are not checked, i.e. the values entered
must be appropriate for the sensor module and the measuring task for the device to be able to
measure correctly.
Description
1
Performing "position adjustment" (
0 L
1000 L
4.5 m
0 m
1
2
3
r
= 1
g
cm
A0017663
1
See table, step 8.
2
See table, step 9.
2
Select the "Level" measuring mode via the
"Measuring mode (005)" parameter.
Menu path: Setup
®
Measuring mode
3
Select a pressure engineering unit via the "Press Eng.
Unit (125)" parameter, here "mbar" for example.
Menu path: Setup
®
Press Eng. Unit
4
Select the "In height" level mode via the "Level
selection (024)" parameter.
Menu path: Setup
®
Extended Setup
®
Level
®
Level selection.