Diagnostics and troubleshooting
Deltabar FMD72
64
"M" messages
Diagnostics event
Cause
Corrective measure
Code
Description
M002
Sens. unknown
Sensor module does not suit the device (electronic sensor
module nameplate). Device continues measuring.
Contact Hauser
Service
M283
Memory content
• Cause as indicated for F283.
• Correct measurement can continue as long as you do
not need the peakhold indicator function.
• Perform a reset
• Replace electronics
M431
Adjustment
The calibration carried out would cause the nominal
sensor module range to be exceeded or undershot.
• Check the measuring
range
• Check position
adjustment
• Check the setting
M434
Scaling
• Values for calibration (e.g. lower range value and upper
range value) are too close together.
• Lower range value and/or upper range value
undershoot or overshoot the sensor module range
limits.
• The sensor module was replaced and the customer-
specific configuration does not suit the sensor.
• Unsuitable download carried out.
• Check the measuring
range
• Check the setting
• Contact Endress
+Hauser Service
M438
Dataset
• The supply voltage is disconnected when writing.
• An error occurred when writing.
• Check the setting
• Restart device
• Replace electronics
"C" messages
Diagnostics event
Cause
Corrective measure
Code
Description
C412
Write Backup
Downloading.
Wait for download to
complete.
C482
Simul. output
Simulation of the current output is switched on, i.e. the
device is not measuring at present.
End the simulation
C484
Error simul.
Fault state simulation is switched on, i.e. the device is not
measuring at present.
End the simulation
C824
Process pressure
• Electromagnetic effects outside the permitted range.
• Overpressure or low pressure present.
• This message appears for a short time only.
• Check the pressure
value
• Restart device
• Perform a reset
"S" messages
Diagnostics event
Cause
Corrective measure
Code
Description
S140
Working range P LP/HP • Overpressure and low pressure present.
• Electromagnetic effects outside the permitted range.
• Sensor module defective.
• Check the process
pressure
• Check the pressure
value
S822
Process temp. LP/HP
• The temperature measured in the sensor module is
greater than the upper nominal temperature of the
sensor module.
• The temperature measured in the sensor module is
smaller than the lower nominal temperature of the
sensor module.
• Check temperature
• Check the setting
S841
Sensor range
• Overpressure or low pressure present.
• Sensor module defective.
• Check the pressure
value
• Contact Endress
+Hauser Service