70
Reference Manual
00809-0100-4772, Rev FA
March 2016
PD_TAG
70
PD tag description of device.
RECOMMENDED_ACTION
78
Enumerated list of recommended actions displayed with a device alert.
RESTART
16
RESTART allows a manual restart to be initiated. Several degrees of restart are
possible:
1 Run: Nominal state when not restarting
2 Restart resource: Not used
3 Restart with defaults: Set parameters to default values (see
START_WITH_DEFAULTS below for which parameters are set).
4 Restart processor: Does a warm start of CPU
RS_STATE
07
RS_STATE represents the state of the function block application state
machine.
SAVE_CONFIG_BLOCKS
FD_MAINT_ALARM
57
This parameter represents the number of EEPROM blocks that have been
modified since the last burn. This value will count down to zero when the
configuration is saved.
SET_FSTATE
29
Allows the FAULT_STATE condition to be manually initiated by selecting Set.
SHED_RCAS
26
SHED_RCAS represents the time duration at which to give up on computer
writes to function block RCas locations.
SHED_ROUT
27
SHED_ROUT represents the time duration at which to give up on computer
writes to function block ROut locations.
SOFTWARE_REV
69
Manufacturer software revision.
ST_REV
01
ST_REV is the revision level of the static data associated with the function
block. The revision value will be incremented each time a static parameter
value in the block is changed.
STRATEGY
03
The strategy field can be used to identify grouping of blocks. These data are
not checked or processed by the block.
TAG_DESC
02
TAG_DESC is the user description of the intended application of the block.
TEST_RW
08
TEST_RW is a parameter for a host to use to test reading and writing (not used
by the device at all).
UPDATE_EVT
35
This alert is generated by any change to the static data.
WRITE_ALM
40
This alert is generated if the write lock parameter is cleared.
WRITE_LOCK
34
If set, no writes from anywhere are allowed, except to clear WRITE_LOCK.
Block inputs will continue to be updated.
WRITE_PRI
39
This parameter specifies the priority of the alarm generated by clearing the
write lock.
Table 5-1. Resource Block Parameters
Parameter
Index
number
Description
Aotewell Ltd
www.aotewell.com
Industry Automation
HongKong|UK|China
+86-755-8660-6182