68
Reference Manual
00809-0100-4772, Rev FA
March 2016
FD_FAIL_PRI
59
This parameter allows the user to specify the priority of this alarm category.
FD_MAINT_ACTIVE
45
This parameter reflects the error conditions that are being detected as active
as selected for this category. It is a bit string, so that multiple conditions may
be shown.
FD_MAINT_ALARM
57
This parameter is used primarily to broadcast a change in the associated
active conditions, which are not masked, for this alarm category to a Host
System.
FD_MAINT_MAP
49
This parameter maps conditions to be detected as active for this alarm
category. Thus the same condition may be active in all, some, or none of the
four alarm categories.
FD_MAINT_MASK
53
This parameter allows the user to suppress any single or multiple conditions
that are active, in this category, from being broadcast to the host through the
alarm parameter. A bit equal to ‘1’ will mask i.e. inhibit the broadcast of a
condition, and a bit equal to ‘0’ will unmask i.e. allow broadcast of a condition.
FD_MAINT_PRI
61
This parameter allows the user to specify the priority of this alarm category.
FD_OFFSPEC_ACTIVE
44
This parameter reflects the error conditions that are being detected as active
as selected for this category. It is a bit string, so that multiple conditions may
be shown.
FD_OFFSPEC_ALARM
56
This parameter is used primarily to broadcast a change in the associated
active conditions, which are not masked, for this alarm category to a Host
System.
FD_OFFSPEC_MAP
48
This parameter maps conditions to be detected as active for this alarm
category. Thus the same condition may be active in all, some, or none of the
four alarm categories.
FD_OFFSPEC_MASK
52
This parameter allows the user to suppress any single or multiple conditions
that are active, in this category, from being broadcast to the host through the
alarm parameter. A bit equal to ‘1’ will mask i.e. inhibit the broadcast of a
condition, and a bit equal to ‘0’ will unmask i.e. allow broadcast of a condition.
FD_OFFSPEC_PRI
60
This parameter allows the user to specify the priority of this alarm category.
FD_RECOMMEN_ACT
64
This parameter is a device enumerated summarization of the most severe
condition or conditions detected. The DD help should describe by
enumerated action, what should be done to alleviate the condition or
conditions. 0 is defined as Not Initialized, 1 is defined as No Action Required,
all others defined by manufacturer.
FD_SIMULATE
63
This parameter allows the conditions to be manually supplied when
simulation is enabled. When simulation is disabled both the diagnostic
simulate value and the diagnostic value track the actual conditions. The
simulate jumper is required for simulation to be enabled and while simulation
is enabled the recommended action will show that simulation is active.
FD_VER
42
This parameter's value equals to the value of the major version of the Field
Diagnostics specification that this device was designed to.
FEATURES
17
This parameter is used to show supported resource block options.
FEATURES_SEL
18
This parameter is used to show selected resource block options. The
flowmeter supports the following options:
Unicode: Tells host to use unicode for string values
Reports: Enables alarms; must be set for alarming to work
Software Lock: Software write locking enabled but not active; WRITE_LOCK
must be set to activate.
Hardware Lock: Hardware write locking enabled but not active; WRITE_LOCK
follows the status of the security switch.
FINAL_ASSY_NUM
74
The same final assembly number placed on the neck label.
Table 5-1. Resource Block Parameters
Parameter
Index
number
Description