47
Reference Manual
00809-0100-4772, Rev FA
March 2016
ELEC_TEMP_RANGE
108
This parameter reports the measurement range of the electronics
temperature sensor (MTA model).
Upper sensor range = 90 °C
Lower sensor range = -55 °C
ELECTRON_TEMP
107
In an MTA model transmitter the electronics temperature is available.
This parameter will report the current temperature of the electronics in
engineering units configured in ELECTRON_TEMP_UNITS
ELECTRON_TEMP_UNITS
93
In an MTA model transmitter the electronics temperature is available.
This parameter is used to configure the engineering units of the
electronics temperature.
ELECTRONICS_STATUS
70
This parameter represents the transducer block electronics status. See
FACTORY_INFO_FLOAT
80
For factory use only.
FACTORY_INFO_INDEX
79
For factory use only.
FACTORY_INFO_U16
82
For factory use only.
FACTORY_INFO_U32
83
For factory use only.
FACTORY_INFO_U8
81
For factory use only.
FILTER_AUTO_ADJUST
LOW_PASS_CODE
42
Selecting a fluid density close to the process density will adjust the
Trigger Level, Low Flow Cutoff, and Low Pass Filter to values that will work
well for most applications.
FILTER_RESTORE
43
This parameter will restore the Low Flow Cutoff, Low Pass Filter, and
Trigger Level to default configurations base on the mass of air for gas
process fluids or the mass of water for liquid process fluids.
1 = Normal state, 2 = Restore filters to defaults.
FIXED_PROC_DENSITY
50
The configured density of the process fluid is used to calculate flow when
mass units are selected.
FIXED_PROC_DENSITY_UNITS
51
The engineering units of PROCESS_DENSITY:
1097 = kilograms per cubic meter
1107 = pounds per cubic foot
FIXED_PROC_TEMP_UNITS
53
The engineering units of process temperature:
1001 = °C
1002 = °F
FIXED_PROC_TEMPERATURE
52
Process temperature is the configured temperature of the process fluid,
in units of °C or °F. This parameter is used to compensate the K-factor for
meter body expansion due to temperature. It is also used to calculate the
PROCESS_DENSITY_RATIO.
FLANGE_TYPE
36
Flange type specifies the wafer or the flange construction material (i.e.
ASME 150, ASME 300, ASME 600, PN64, JIS 10K, etc.). Flange type is
used as an input to the compensated K-factor calculation.
INSTALLATION_EFFECTS
32
An adjustment to the Compensated K-Factor to account for less than
ideal upstream piping effects.
K_FACTOR
31
The K-factor is the meter body calibration number. Units are reflected in
K_FACTOR_UNITS.
K_FACTOR_UNITS
34
K-factor units are the engineering units to be applied to the K_FACTOR
and COMPD_K_FACTOR.
0 = Pulses per gallon
LFC_IN_ENG_UNITS
45
This read-only parameter will indicate Low Flow Cutoff in currently
configured engineering units.
Table 4-1. Transducer Block Parameters
Parameter
Index
number
Definition