3.23.2
Installation steps
Follow these steps to install the WSP saddle seal:
Procedure
1. Prepare the tank and weld the saddle lower onto the tank per plant procedures.
Ensure the saddle lower is not assembled to the pressure transmitter and/or the
remote seal prior to welding.
CAUTION
Excessive heat will distort the saddle lower. Allow adequate cooling time between
passes.
2. Remove the protective cover from the diaphragm of the remote seal. Use extreme
caution during installation to ensure the diaphragm is not damaged.
3. Place the appropriate gasket for the application on the remote seal.
WARNING
Failure to properly install the gasket may cause process leaks, which can result in
death or serious injury.
4. Insert the WSP saddle seal into the saddle lower.
5. Install the bolts in a cross pattern and hand-tighten.
6. Using a torque wrench on the bolt, tighten the assembly in a cross-pattern to
). The bolts should be torqued to 180
in-lb (20 N-m) with stainless or carbon steel bolts. Consider leak checking the
installation to ensure a robust connection.
3.24
UCP union connection pipe mount seal
Figure 3-31: UCP Threaded Pipe Mount Seal
A
B
A. Connection to transmitter
B. Diaphragm
Installation
Reference Manual
May 2020
00809-0100-4002
64
Rosemount DP Level
Summary of Contents for Rosemount 1199
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual May 2020 00809 0100 4002 8 Rosemount DP Level ...
Page 22: ...Remote Seal Systems Reference Manual May 2020 00809 0100 4002 22 Rosemount DP Level ...
Page 74: ...Installation Reference Manual May 2020 00809 0100 4002 74 Rosemount DP Level ...
Page 92: ...Fill Fluids Reference Manual May 2020 00809 0100 4002 92 Rosemount DP Level ...