Figure 2-5: Balanced System
+3.6 inH
2
O
(9.0 mbar)
Head temperature
effect
No error
(Cancels out)
Seal temperature
effect
+3.6 inH
2
O
(9.0 mbar)
Total temperature
effect on system
Note
Temperature effects were calculated in Instrument Toolkit using a 2-in. (DN 50) FFW seal,
Silicone 200, 10 ft. (3 m) between the taps, over a 50 °F (28 °C) temperature change.
Tuned-Systems assemblies are asymmetrical remote seal systems with one seal directly
mounted to the high side of the differential pressure transmitter, and the other side
connected to a seal via capillary. Another possible Tuned-System assembly is any remote
seal system with unequal lengths of capillary or two different remote seals on the high and
low pressure connections. Due to the unequal lengths of capillary, there are seal
temperature effects. However, this seal temperature effect counters the head pressure
from the oil-filled capillary and reduces total temperature effects on the entire system.
Figure 2-6: Tuned-System Assembly
Head temperature
effect
+3.6 inH
2
O
(9.0 mbar)
Seal temperature
effect
-1.7 inH
2
O
(4.2 mbar)
Total temperature
effect on system
+1.9 inH
2
O
(4.7 mbar)
Note
Temperature effects were calculated in Instrument Toolkit using a 2-in. (DN 50) FFW seal,
Silicone 200, 10 ft. (3 m) between the taps, over a 50 °F (28 °C) temperature change.
Reference Manual
Remote Seal Systems
00809-0100-4002
May 2020
Rosemount DP Level
13
Summary of Contents for Rosemount 1199
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual May 2020 00809 0100 4002 8 Rosemount DP Level ...
Page 22: ...Remote Seal Systems Reference Manual May 2020 00809 0100 4002 22 Rosemount DP Level ...
Page 74: ...Installation Reference Manual May 2020 00809 0100 4002 74 Rosemount DP Level ...
Page 92: ...Fill Fluids Reference Manual May 2020 00809 0100 4002 92 Rosemount DP Level ...