2.7
Differences between electronic remote sensors
and capillary systems
Rosemount 3051S Electronic Remote Sensors (ERS
™
) System technology utilizes two
Rosemount 3051S Pressure Transmitters connected via an electrical wire instead of a
single pressure transmitter with remote seals and capillary tubing. As the Rosemount
3051S ERS System calculates the differential pressure between the two transmitters,
capillary tubing is not needed, and thus eliminates all head temperature affects on the
system. Seals are not required, but may still be necessary on certain applications that
include high temperature, corrosive, or viscous processes. For more information, refer to
the Rosemount 3051S Series
Figure 2-7: ERS vs. Capillary
Rosemount 3051S ERS
Traditional capillary system
A
B
A. Non-proprietary electrical cable
B. Oil-filled capillary system
2.8
Instrument Toolkit: seal ordering and
application process
Rosemount Instrument Toolkit Software is an instrumentation specification tool that can
be used to assist in product selection. This program analyzes application and process
conditions against a configured Rosemount model number and calculates the total system
performance including expected head and seal temperature effects and system response
times.
Visit the Emerson website for information on how to obtain and use Instrument Toolkit.
Reference Manual
Remote Seal Systems
00809-0100-4002
May 2020
Rosemount DP Level
17
Summary of Contents for Rosemount 1199
Page 4: ...4 ...
Page 8: ...Introduction Reference Manual May 2020 00809 0100 4002 8 Rosemount DP Level ...
Page 22: ...Remote Seal Systems Reference Manual May 2020 00809 0100 4002 22 Rosemount DP Level ...
Page 74: ...Installation Reference Manual May 2020 00809 0100 4002 74 Rosemount DP Level ...
Page 92: ...Fill Fluids Reference Manual May 2020 00809 0100 4002 92 Rosemount DP Level ...