RSTI-EP PROFINET I/O Controller User Manual
Section 3
GFK-2571R
May 2021
Configuration
73
CAT Number
Description
IC200ALG430
Analog Mixed Module, Input Current 4 Channels, Output Current 2
Channels
IC200ALG431
Analog Mixed Module, 0 to +10Vdc Input 4 Channels, Output 0 to
+10Vdc 2 Channels
IC200ALG432
Analog Mixed Module, 12-bit -10 to +10Vdc, Input 4 Channels / Output -
10 to +10Vdc 2 Channels
All VersaMax Analog modules, except MDD841 and ALG331, support a default Analog value
of zero only.
Before their parameters can be configured, these modules require an additional
configuration step in Machine Edition after being added to the PNS remote node.
When one of the above modules is added to the Configuration, the Navigator window shows
a Configuration Mismatch for the module (and for its PNS). This situation needs to be
resolved before continuing, as described in below Section.
Figure 69 shows a configuration in which two modules have this type of mismatch:
Figure 69: Analog Modules Requiring Jumper-Setting Designation
Double-clicking one of these modules, or right-clicking and selecting Configure displays
only the Power Consumption and GSDML tabs. The Settings tab and other configuration
tabs do not appear. To begin configuring one of these modules, right-click the module in
the Navigator and select Change Submodule List from the menu.
The Change Submodule List
On the Change Submodule List, select the type of inputs or outputs that will be wired to the
module, and drag the selection to the Content field in the left pane. For example:
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...