To open the DCP tool, right-click the hardware configuration slot containing the
IC695PNC001 PROFINET Controller and choose Launch Discovery Tool from the menu. Use
the Connection dropdown list to select the computer port being used by the programmer
to communicate with the RX3i system:
Figure 85: Use of Connection Drop-Down List
The choices should match the windows network setting in the computer’s network control
panel.
Figure 86: Equivalent Windows Network Settings
In the DCP tool, use the LAN list to select the configured LAN. The results will be validated
against the selected LAN.
Figure 87: Assign LAN
Once a LAN is selected, click on
Refresh Device List
to display a list of actual devices on the
LAN. Each device can be in one of three conditions as indicated by the symbol in the
Status
column:
indicates that the
Device Name, IP Address, Subnet
and
Gateway
of the actual device
matches the configured device of the same
Device Name
residing on the selected LAN.