RSTI-EP PROFINET I/O Controller User Manual
Section 5
GFK-2571R
May 2021
Diagnostics
120
Group/
Category/
Type/
Descriptor
Description
Cause
Recommended
Correction
9-18-1-1
PNC001
module
exceeded its
recommended
operating
temperature.
The
temperature
detected by the
PNC001 module
has exceeded its
safe operating
temperature.
Reduce the temperature of the environment
where the PNC001 module is operating.
9-18-1-2
Watchdog
Timeout Error
PNC001
application
code restarted
due to a
hardware
watchdog
timeout.
Contact customer service.
9-69-0-0
PROFINET
Controller has
become
heavily
loaded.
The PROFINET
Controller has
become heavily
loaded with
activity.
PROFINET
Controller is
running at or
above the
maximum
supported load.
I/O updates
experienced by
the PLC may be
slower than
optimal. Refer
to Section 3.1.1.
No action is required if no PROFINET system
performance is observed. If action is required to
run the PROFINET Controller at or below the
maximum supported load, reduce the load on
PROFINET Controller, using one or both of the
following methods:
•
Increase the configured update rate value
(i.e. IO received less frequently) of one or
more PROFINET Devices configured on the
PROFINET Controller.
•
Reduce the number of PROFINET Devices
configured on the PROFINET Controller.
9-70-0-0
PROFINET
Controller is
no longer
heavily
loaded.
Load applied to
PROFINET
Controller has
been reduced to
or below the
maximum
supported load,
after it was
previously
heavily loaded.
None.
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...