RSTI-EP PROFINET I/O Controller User Manual
Section 5
GFK-2571R
May 2021
Diagnostics
108
Group/
Error Code
Description
Cause
Recommended
Correction
5-4
CLI PNC specific
command
failure
PNC001 encountered an error
while processing a PNC001-
specific CLI command.
Contact customer service.
5-5
CLI initialization
failure
The Command Line Interface
functionality on the PNC001
failed to initialize correctly.
Contact customer service.
6-1
Write to
nonvolatile
memory failure
The PROFINET Controller failed
to write data to non-volatile
memory, which could result
from configuration store/clear
operations
from
the
programmer, or Command Line
Interface commands.
Contact customer service.
8-1
Return of
Submodule
PROFINET
Alarm received.
The PROFINET Controller has
received
a
Return
of
Submodule PROFINET alarm
from a PROFINET device.
None.
8-2
PROFINET
Submodule
replied
negatively to
Plug
configuration.
The
PROFINET
Controller
received
a
negative
acknowledgement
while
attempting to reconfigure a
PROFINET submodule that had
been plugged back in to a
device.
Attempt reactivation of
submodule, by removing
the
submodule
and
reinserting it into its host
device.
8-3
PROFINET
Controller
failed delivery
of fault to the
PACSystems
controller.
The PROFINET Controller was
unable to deliver to the
PACSystems controller a fault
that was logged locally on the
PROFINET Controller. The fault
will appear in the Local Log of
the PROFINET Controller but
will not appear in the controller
Fault Tables.
Contact customer service.
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...