RSTI-EP PROFINET I/O Controller User Manual
Section 5
GFK-2571R
May 2021
Diagnostics
119
Group/
Category/
Type/
Descriptor
Description
Cause
Recommended
Correction
9-6-13-0
The Media
Redundancy
Manager has
detected that
the network
ring has been
repaired.
The PROFINET
MRP network
ring is
closed/okay.
No action necessary. This is the normal,
expected state of an MRP Ethernet ring.
9-11-3-1
Invalid MAC
address
detected.
PROFINET
Controller no
longer has a
valid MAC
address.
Contact customer service.
9-11-3-3
Media
redundancy
configuration
error.
The PROFINET
Controller has
encountered a
problem
attempting to
configure media
redundancy
operation.
Contact customer service.
9-11-3-4
All critical
network ports
are
disconnected.
The PROFINET
Controller has
detected that all
the configured
critical network
ports
have lost
their links and
are no longer
connected.
Reconnect the configured
critical network ports
.
9-11-5-z
13
Internal
runtime error.
PROFINET
Controller has
encountered an
internal error
during its
operation.
Contact customer service.
13
z: Runtime error detail. Inform value of z to customer support.
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...