RSTI-EP PROFINET I/O Controller User Manual
Section 3
GFK-2571R
May 2021
Configuration
80
3.9
Viewing / Editing IO-Device Properties
In addition to the parameter configuration described on the previous pages, all IO-Devices
(PNS modules and third-party devices) have other configurable properties. These properties
are displayed in the Machine Edition Inspector pane when the device is selected in the
Navigator.
In the Inspector, properties that are not grayed-out can be used as is or edited as
appropriate.
Figure 82: Inspector View of IO-Device Properties
Device Number: a number automatically assigned to the device in the configuration.
Update Rate: The period between PROFINET cyclic data transfers between an IO-Controller
and an IO Device. Defaults to 32ms for RX3i and VersaMax PNS modules, and to 128ms for
third party devices. To change the update period of the PROFINET production cycle for the
IO Device, use the drop-down list to select 1, 2, 4, 8, 16, 32, 64, 128, 256, or 512ms:
Figure 83: Setting of IO-Device Update Rate
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...