RSTI-EP PROFINET I/O Controller User Manual
Section 5
GFK-2571R
May 2021
Diagnostics
100
5.1.2
Problems During Power-up and Reset
Certain conditions can prevent the module from powering up and becoming operational or
entering firmware update mode:
Problem
Indication
Action
Hardware failure
All LEDs off. Module unresponsive. Return the module Emerson.
Invalid bootstrap image
Invalid boot image
No LEDs turn on and the module is
unresponsive, or
The
STATUS
LED is solid green and
is the only LED that is on.
Power-up
diagnostics/hardware
initializations fail that are
considered fatal
LED Fatal Error blink code, as
described in this chapter.
Note the blink code and
contact Customer Service.
Non-Fatal
diagnostic/hardware
initialization faults
The module continues normal
power-up, but an entry is added to
the Local Log table and the RX3i
CPU’s Fault Table (if backplane
communications
have
been
established).
Note the fault and contact
Customer Service.
The module does not
contain hardware identity
information
LED Fatal Error blink pattern, as
described in this chapter.
Note the blink code and
contact Customer Service.
5.1.3
Transitioning to Firmware Update Mode
The module transitions to firmware update mode for any of the following reasons:
1.
WinLoader has commanded the module to enter firmware update mode. This is
normal when a firmware update has been initiated from WinLoader.
2.
The PNC001 does not have a valid firmware image at power-up. The PNC001
performs checks to determine the firmware image is valid and has not been
corrupted before it begins execution. If the validation fails, firmware update mode
is activated until a valid image has been stored.
For more information about firmware update mode and using WinLoader, please see
Section 2:, Installation.
5.2
Special LED Blink Patterns
In addition to the LED blink patterns that indicate a fatal error, the PNC001’s LEDs can
indicate module location/identification and microprocessor overtemperature conditions,
as described below.
Special LED Blink Patterns are not supported by RSTi-EP CPE100/CPE115 embedded
PROFINET Controller.
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...