PROFINET IO Performance Examples
153
System
Configuration
Total # PROFINET
I/O
Devices/Modules
Total
Amount
PROFINET I/O
Discrete
pts./Analog
Chan.
RX3i CPU
Sweep
Time (ms)
Average
(Max)
16 pt.
Discrete I/O
Loopback
Time (ms)
Average
(Min, Max)
A.3
–
Multi-
PNC001 Multi-
Device
32/41
2808/85
7.2 (9.6)
14 (6, 17)
16 ms PROFINET Update Rate
B.1
–
Multi-
Device
20/29
1928/0
5.2 (8.2)
22 (5, 42)
B.1.1
–
Multi-
Device w/MRP
20/29
1928/0
5.2 (7.7)
23 (5, 43)
B.2
–
Max Device
64/89
5176/445
12.3 (15.4)
36 (11, 60)
A-2.2
VersaMax System Descriptions
1ms PROFINET Update Rate Systems
Single Device
This system contained an IC695CPU315, IC695ETM001, and an IC695PNC001 in the main
RX3i rack. The PNC001 was connected to a single VersaMax PNS (IC200PNS001) configured
for a 1 ms PROFINET update rate. The PNS contained four mixed discrete 16 point in/out
modules (IC200MDD844). Each I/O module had its outputs tied to the inputs of an adjoining
I/O module, and each input module was configured with a 1 ms Input DC Filter time. The I/O
Loopback measurement was taken using one of the IC200MDD844 modules.
Multi-Device
This system contained an IC695CPU315, IC695ETM001, and an IC695PNC001 in the main
RX3i rack. The PNC001 was connected in a network bus configuration to eight different
VersaMax PNS modules (IC200PNS001), each configured for a 1ms PROFINET update rate.
Each PNS contained at least one discrete input or output module. The I/O Loopback
measurement was taken using a 16-point output module (IC200MDL741) owned by one
VersaMax PNS, that was then tied to the 16-point input module (IC200MDL640) owned by
a different VersaMax PNS. The input module (IC200MDL640) was configured for a 0 ms
Input DC Filter time.
Multi-Device with MRP
This system is identical to the A.2
–
Multi-Device configuration, except that Media
Redundancy Protocol (MRP) was in use. To exercise MRP, the network was set up in a ring
configuration and the PNC001 was configured as an MRP Manager with a configured Default
Test Interval of 20 ms.
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...