RSTI-EP PROFINET I/O Controller User Manual
Appendix A
GFK-2571R
May 2021
PROFINET IO Performance Examples
155
A-3
Systems with RSTi-EP EPSCPE100/CPE115
A-3.1
RSTi-EP CPE100/CPE115 Embedded PROFINET
Controller System Performance Summary
System
Configuration
Total # of
PROFINET I/O
Devices/
Modules
21
Total
Amount
PROFINET
I/0
Discrete
pts./
Analog
Chan.
RSTi-EP CPU
Sweep Time
(ms)
Average
(Max)
8-pt.
Discrete I/O
Loopback
Time (ms)
Average
(Min, Max)
4-pt.
Analog I/O
Loopback
Time (ms)
Average
(Min, Max)
16 ms PROFINET Update Rate
Single Device
1/10
8/44
2.7(7.17)
25(11,41)
24(11,40)
1/64
188/148
6.9 (13.8)
36 (17, 56)
33(11, 48)
8/96
428/225
11.4 (18.7)
48 (20, 69)
40(18, 57)
4/70
348/173
16.8(26.7)
48(15, 77)
39(12, 61)
A-3.2
RSTi-EP System Descriptions
16ms PROFINET Update Rate Systems
Single Device
This system contained an RSTi-EP Standalone Controller with embedded PROFINET
EPSCPE100/CPE115 and IO Scan in Normal Sweep mode. The embedded Ethernet is
connected to PAC Machine Edition The embedded PROFINET Controller CPE100/CPE115
was connected to a single RSTi-EP PNS (EPXPNS001) configured for a 16ms PROFINET
update rate. The PNS contained 10 I/O modules with combinations of discrete 4 point in/out
modules & analog 4/6 channel in/out modules. Each I/O module had its outputs tied to the
inputs of an adjoining I/O module. The total data Bytes size is 122. The I/O Loopback
21
Number of modules includes I/O modules only; does not include head-ends or power-supplies.
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...