Diagnostics
107
PROFINET Controller Faults in the PACSystems Fault Tables section of this chapter, are not
repeated here.
Group/
Error Code
Description
Cause
Recommended
Correction
2-1
PNC001
restarted.
The PNC001 has experienced a
restart. Possible causes include:
-
PNC001 power-cycled
-
PNC001 reset button
pushed
-
PNC001 command shell
command to reset board
issued
-
PNC001 firmware
updated
-
PNC001 exceeded safe
operating temperature
-
PNC001 hardware
watchdog timer expired
-
PNC001 internal fatal
error encountered
The reason for the reset is
indicated by the description
shown when displaying the
fault.
If the PNC001 restart is due
to a hardware watchdog
timer expiration, or internal
fatal error, note the Fault
Extra Data and contact
customer service.
2-2
Time
synchronization
with
PACSystems
RX3i controller
failed.
The PNC001 was unable to
synchronize its current time
with the PACSystems RX3i
controller.
Contact customer service.
2-4
Invalid Media
Redundancy
Configuration
PROFINET Controller
encountered an error related to
applying Media Redundancy
configuration parameters.
Contact customer service.
4-1
Socket close
failed
PROFINET Controller was
unable to close an opened OS
socket.
Contact customer service.
5-1
CLI null
environment
pointer
PNC001 encountered a null
pointer while processing a
command via the CLI.
Contact customer service.
5-3
CLI Ethernet
command
failure
PNC001 encountered an error
while processing an Ethernet
related command.
Contact customer service.
Summary of Contents for PACSystems RX3i
Page 46: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 39 ...
Page 51: ...RSTI EP PROFINET I O Controller User Manual Section 2 GFK 2571R May 2021 Installation 44 ...
Page 72: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 65 ...
Page 82: ...RSTI EP PROFINET I O Controller User Manual Section 3 GFK 2571R May 2021 Configuration 75 ...