You can configure the sensor index only if the connection is through a service port. If the
connection is an RS-485 port, the sensor index is read-only, with each Modbus address
corresponding to a different sensor. In default, Modbus address 1 corresponds to sensor 1,
Modbus address 2 corresponds to sensor 2.
5.3.2
Configure the RTD cable length
ProLink III
Device Tools
>
Configuration
>
Informational Parameters
>
Sensor
>
RTD1(2) Cable Length
Overview
Configure the RTD cable length if your 9-wire cable length is other than three meters.
Prerequisites
Verify that the sensor index is correct.
Procedure
Enter the cable length (unit:m) in the
RTD 1(2) Cable Length
field.
Related information
5.3.3
Configure
Sensor Serial Number
ProLink III
Device Tools
>
Configuration
>
Informational Parameters
>
Sensor
Overview
Sensor Serial Number
lets you store the serial number of the sensor component of your
flowmeter in transmitter memory. This parameter is not used in processing and is not
required.
Procedure
1.
Obtain the sensor serial number from your sensor tag.
2.
Enter the serial number in the
Sensor Serial Number
field.
5.3.4
Configure
Sensor Material
ProLink III
Device Tools
>
Configuration
>
Informational Parameters
>
Sensor
Configure device options and preferences
Configuration and Use Manual
41
Summary of Contents for Micro Motion LNG Series
Page 1: ...Configuration and Use Manual MMI 20032809 Rev AA February 2017 Micro Motion LNG Series Meters ...
Page 6: ...Contents iv Micro Motion LNG Series Meters ...
Page 8: ...Getting Started 2 Micro Motion LNG Series Meters ...
Page 12: ...Before you begin 6 Micro Motion LNG Series Meters ...
Page 18: ...Quick start 12 Micro Motion LNG Series Meters ...
Page 20: ...Configuration and commissioning 14 Micro Motion LNG Series Meters ...
Page 50: ...Configure device options and preferences 44 Micro Motion LNG Series Meters ...
Page 56: ...Integrate the meter with the control system 50 Micro Motion LNG Series Meters ...
Page 58: ...Complete the configuration 52 Micro Motion LNG Series Meters ...
Page 60: ...Operations maintenance and troubleshooting 54 Micro Motion LNG Series Meters ...
Page 74: ...Measurement support 68 Micro Motion LNG Series Meters ...
Page 94: ...Using ProLink III with the transmitter 88 Micro Motion LNG Series Meters ...
Page 98: ...Default values and ranges 92 Micro Motion LNG Series Meters ...
Page 99: ...Default values and ranges Configuration and Use Manual 93 ...