5.2
Configure alert handling
The alert handling parameters control the transmitter’s response to process and device
conditions.
•
(Section 5.2.1)
•
(Section 5.2.2)
5.2.1
Configure
Fault Timeout
ProLink III
Device Tools
>
Configuration
>
Fault Processing
Overview
Fault Timeout
controls the delay before fault actions are performed.
Restriction
Fault Timeout
is applied only to the following alerts (listed by Status Alert Code): A003, A004, A005,
A008, A016, A033. For all other alerts, fault actions are performed as soon as the alert is detected.
Procedure
Set
Fault Timeout
as desired.
The default value is 0 seconds. The range is 0 to 60 seconds.
If you set
Fault Timeout
to 0, fault actions are performed as soon as the alert condition is
detected.
The fault timeout period begins when the transmitter detects an alert condition. During
the fault timeout period, the transmitter continues to report its last valid measurements.
If the fault timeout period expires while the alert is still active, the fault actions are
performed. If the alert condition clears before the fault timeout expires, no fault actions
are performed.
5.2.2
Configure
Status Alert Severity
ProLink III
Device Tools
>
Configuration
>
Alert Severity
Overview
Use
Status Alert Severity
to control the fault actions that the transmitter performs when it
detects an alert condition.
Configure device options and preferences
38
Micro Motion
®
LNG Series Meters
Summary of Contents for Micro Motion LNG Series
Page 1: ...Configuration and Use Manual MMI 20032809 Rev AA February 2017 Micro Motion LNG Series Meters ...
Page 6: ...Contents iv Micro Motion LNG Series Meters ...
Page 8: ...Getting Started 2 Micro Motion LNG Series Meters ...
Page 12: ...Before you begin 6 Micro Motion LNG Series Meters ...
Page 18: ...Quick start 12 Micro Motion LNG Series Meters ...
Page 20: ...Configuration and commissioning 14 Micro Motion LNG Series Meters ...
Page 50: ...Configure device options and preferences 44 Micro Motion LNG Series Meters ...
Page 56: ...Integrate the meter with the control system 50 Micro Motion LNG Series Meters ...
Page 58: ...Complete the configuration 52 Micro Motion LNG Series Meters ...
Page 60: ...Operations maintenance and troubleshooting 54 Micro Motion LNG Series Meters ...
Page 74: ...Measurement support 68 Micro Motion LNG Series Meters ...
Page 94: ...Using ProLink III with the transmitter 88 Micro Motion LNG Series Meters ...
Page 98: ...Default values and ranges 92 Micro Motion LNG Series Meters ...
Page 99: ...Default values and ranges Configuration and Use Manual 93 ...