COUNTER OPERATORS
COUNTER operator is a pulse counter that sets output Q to 1 (TRUE) as soon as the desired
count is reached.
COUNTER (max number = 8).
The operator COUNTER is a pulse counter.
There are 3 operationg modes:
1) AUTOMATIC
2) MANUAL
3) AUT MANUAL
1) The counter generates a pulse of duration
equal to the system response time as soon as
the set count is reached. If the CLEAR pin is
not enabled this is the default mode.
2) The counter leads to 1 (TRUE) the output Q as
soon as it reaches the set count. The output Q
goes to 0 (FALSE) when the signal CLEAR is activated.
3) The counter generates a pulse of duration equal to the system response time as soon as the set
count is reached. If the CLEAR signal is activated, the internal count goes back to 0.
Parameters
Clear Enable
: If selected this enables the request to clear in order to restart the counter setting
output Q to 0 (FALSE). It also offers the possibility of enabling or not enabling (
Automatic Enable
)
automatic operation with manual reset.
If this is not selected the operation is automatic. Once the set count is reached output Q is set to
1(TRUE) and stays in this condition for two internal eloProg cycles after which it is resetted.
Ck down
: Enables counting down.
Two-way
: If selected it enables counting on both the rising and falling edges.
TIMER OPERATORS (max number = 8)
TIMER operators allow you to generate a signal (TRUE or FALSE) for a user-definable period.
CLOCKING
CLOCKING operator generates a clock signal output
with the desired period if the input In is 1 (TRUE).
Parameters
Time
: The period can be set to between
10 ms and
1093.3 s.