OUTPUTS
OUT STATUS
The OUT STATUS signal is a programmable digital output that can indicate the status of:
• An
input.
• An
output.
• A node of the logic diagram designed using the configuration software.
OUT TEST
The OUT TEST signals must be used to monitor the presence of short-circuits or overloads on the
inputs (Figure 5).
Figure 5
Î
The maximum number of controllable inputs for
each output OUT TEST is:
- 2 INPUT (parallel connection)
(485EPB,
485EPE0802, 485EPE08)
- 4 INPUT (parallel connection)
(485EPE16)
OSSD (485EPB, 485EPE08A02, 485EPA02, 485EPA04)
The OSSD
(static semiconductor safety outputs)
are short circuit protected, cross circuit monitored
and supply:
• In the ON condition:
Uv-0,75V ÷ Uv (where Uv is 24V ± 20%)
• In the OFF condition:
0V ÷ 2V r.m.s.
The maximum load of 400mA@24V corresponds to a minimum resistive load of 60
Ω
.
The maximum capacitive load is 0.82
μ
F. The maximum inductive load is 30mH.
Î
The connection of external devices to the outputs is not allowed, except as expected in the
configuration performed with the software.
Each OSSD output can be configured as shown in Table 12:
Automatic
The output is activated according to le configurations set by the software only if the corresponding
RESTART_FBK input is connected to 24VDC.
Manual
The output is activated according to le configurations set by the software only if corresponding
RESTART_FBK input FOLLOWS A LOGIC TRANSITION OF
0-->1.
Monitored
The output is activated according to le configurations set by the software only if the corresponding
RESTART_FBK input FOLLOWS A LOGIC TRANSITION OF
0-->1-->0.
Table 12