eloProg - Vers. 1.0
37
485EPE08A02
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL
IN1÷8
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
RED/GREEN
YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical address
of the unit
OFF
Red
OFF
OFF
Replace the module
Compatibility error
OFF
5
flashes
OFF
5 flashes
5
flashes
5
flashes
5
flashes
• Firmware version not
compatible with
485EPB, return to
elobau for FW upgrade.
OSSD output error
OFF
4
flashes
OFF OFF
4 flashes
(only the LED
corresponding to the
output in FAIL mode)
OFF OFF
• Check OSSD1/2
connections
• If the problem persists,
replace the module
Error in
communication with
master
OFF
5
flashes
OFF OFF
OFF
OFF OFF
• Restart the system
• If the problem persists,
replace the module
Error on other
slave or master
OFF
ON
OFF OFF
OFF
OFF OFF
• Restart the system
• Check which unit is in
FAIL mode
Same type of slave
with same address
detected
OFF
5
flashes
5
flashes
OFF OFF
OFF OFF
• Change the unit's
address (see
NODE
SEL
)
Table 39 - Troubleshooting 485EPE08A02
Figure 19