eloProg - Vers. 1.0
39
485EPE16
MEANING
LED
REMEDY
RUN
IN FAIL
EXT FAIL
SEL
IN1÷16
OSSD1/2
CLEAR1/2
STATUS1/2
GREEN
RED
RED
ORANGE
YELLOW
RED/GREEN
YELLOW
YELLOW
Internal fault
OFF
2 or 3
flashes
OFF
Shows the
physical address
of the unit
OFF
Red
OFF
OFF
Replace the module
Compatibility error
OFF
5
flashes
OFF
5
flashes
5
flashes
5
flashes
5
flashes
• Firmware version not
compatible with 485EPB,
return to elobau for FW
upgrade.
Error in communication
with master
OFF
5
flashes
OFF OFF
OFF
OFF OFF
• Restart the system
• If the problem persists
replace the module
Error on other
slave or master
OFF
ON
OFF OFF
OFF
OFF OFF
• Restart the system
• Check which unit is in FAIL
mode
Same type of slave with
same address detected
OFF
5
flashes
5
flashes
OFF OFF
OFF OFF
• Change the unit's address
(see
NODE SEL
)
Table 41 - Troubleshooting 485EPE16
Figure 21