KOMET 200 - 600
10
Controller MO 36
10.1
Electrical installation
The leads must be inserted from below. For gates with two wings a minimum
cross section [mm²] of the lead is necessary, which is determined by the
length of the lead between the 2.opener and the controller.
Cross sections selected too small will have adverse effect on the motor
performance.
For the gate openers (with controller MO 36) the following lead dimensions are
required:
Cross section:
5 x 1,5mm²
up to
15m
distance
Cross section:
5 x 2,5mm²
up to
20m
distance
Power supply for the controller:
230Vac, 50Hz, single Phase
Connection:
By fixed wiring and main switch (on site) or flexible wiring with
cable stress relief device according to the European standards.
The provided motor cable is only suitable for the short way to the connection
box; a mechanical protection should be used where applicable. For the longer
connection distance between gate opener and controller please use a suitable
cable. Here also use a mechanical protection (conduit) if applicable.
REMARK!
For the connection of the motor lead to the controller MO 36 use
solely leads with flexible conductors, like e.g. ÖLFLEX ROBUST 210.
Cable configuration:
Mark
Contacts on the MO 36
1 GND
2 IMP
3 I+
4 M-
5 M+
Table 6
23