KOMET 200 - 600
10.3.1.6
Sequence P6: Automatic closure for complete opening
When sequence
P6
is activated by
button LERN
, the present value for stay-
open time for complete opening is displayed. Possible values are
--
(not
activated), 01 up to 299 (for 1s -299s). The value can be
increased using
button BT
and
decreased using button BTG
. The decimal dots of the
display are each equal to 100 (one lit dot = 100 / two lit dots = 200).
Display(example) Corresponds
to:
--
Automatic closure is deactivated.
23
Automatic closure is activated. Stay-open time 23
seconds.
2.3
Automatic closure is activated. Stay-open time 123
seconds.
2.3.
Automatic closure is activated. Stay-open time 223
seconds.
Table 17
Return to the learning sequence using
button LERN
.
When using automatic closure both wings close automatically after the learned
stay-open time has elapsed. The stay-open time starts elapsing when the last
wing has reached the position OPEN.
When contact BS is opened, the automatic closure function is blocked.
When the stay-open time has elapsed and the safety contact profile for
direction CLOSE (SLZ) is currently activated, the gate remains open. The
elapsed stay-open time will not be repeated. When the SLZ is not
activated anymore and the stay-open time has elapsed, the warning time
prior to closing starts.
When the automatic closure function is blocked it will be reactivated with a
new signal (BA or BT).
When the lockage function for the photo-cells is activated, the automatic
closure function is blocked, as long as an obstacle is present between the
photo-cells (see sequence PB).
When the gate hits an obstacle during closing and reversing is activated
through SLZ, the gate opens. When automatic closure is activated and the
obstacle is not removed, the gate will try to close twice. After hitting the
obstacle for the second time the gate will reverse for a short distance and
stop.- The counting will be erased when using BT, BA, or BZ.
32