KOMET 200 - 600
10.2.5
Output terminals
Output Connection
Corresponds
to:
Motor
pedestrian
wing
and IMP
g
5 pin
Connection for 24Vdc motor and pulser for
the pedestrian wing
Motor main
wing
and IMP
f
5 pin
Connection for 24Vdc Motor and pulser for
the main wing or for one-winged gates
SCHLOSS
3 pin
Connection for electromagnetic bolt or
magnetic lock with 24Vdc (max. 1A)
WARN
2 pin
Potential-free contact for warning light
230Vac /max. 60W
MULTI
2 pin
Potential-free contact for multi-functional
relays(230Vac / max. 60W)
Uext
3 pin
24Vdc and 12Vdc, mutual ground terminal,
stabilised direct voltage, together max.
300mA, ground terminal is connected with
controller ground
LS-TEST
1 pin
24Vdc for photo-cell transmitter
PE 1
pin Earth
AMPEL
2 pin
Socket for traffic light module AMO34A red /
green
Table 10
10.3
Programming MO36
For programming and to set operating parameters, use the two-digit 7-
segment display and the buttons BT, BTG and LERN.
At least the following sequences have to be learned as basic
configuration:
P1
- Learning of running distance
P2
- Selecting of force and speed
PC
- Pressure relief of electromechanical bolt (mandatory when
using optional internal blocking)
10.3.1
Learning sequence
During normal operation the display is off.
The learning sequence is
activated by pushing the button LERN for approx. 2s
. The display shows
P1
. The sequence 1 is pre-set. With the button
BT
you can move on to the
next sequence
P2
,
P3
etc. With the button
BTG
you can move back to the
last sequence. When the required sequence is displayed it has to be activated
with the button
LERN
.
Sequence Function
p1
Selection one wing / two wings
27