Meldungen POS: XXXXX
Input
Default
Fremdlüfter X
External fan
-, 0..99 2
Notbetrieb X
Emergency operation
-, 0..99 0
Änderg.Transmit. X
Sensor calibration change
-, 0..99 0
Aut. Sperre Verd X
Automatic compressor lock
-, 0..99 2
Messkreis MD X
Fault in medium pressure measuring circuit
-, 0..99 1
Messk.Gask.aust. X
Fault in gas cooler outlet temperature measuring circuit
-, 0..99 1
Schalth.zu hoch X
Too many starts (LP combined control)
-, 0..99 0
Kein Lastgrad X
No load level received (t
0
-shift)
-, 0..99 0
Stör HD-Ventil X
Fault in the high pressure valve
-, 0..99 0
MD zu hoch X
Medium pressure too high
-, 0..99 2
Drehz.steller HD X
HP speed controller fault for HP combined control
-, 0..99 2
Messk.WRG-Aust. X
Fault in the heat recovery temperature measuring circuit
-, 0..99 -
Messk_ÜH-K X
Measuring circuit error in the suction gas temperature sensor for establishing the
superheat on the case side
-, 0..99 0
ÜH-K zu klein X
Suction gas superheat too low on the case side
-, 0..99 0
Stör MD-Ventil X
Fault in the medium pressure valve
-, 0..99 0
NK-Steuerung X
NT controller not accessible or faulty
-, 0..99 2
Messkreis ND Z2 X
Low pressure Z2 measuring circuit error
-, 0..99 2
Auslastg.Verfl. X
Condenser utilisation too high – condenser soiled
-, 0..99 0
ÜH-V zu klein X
Suction gas superheat too small on the pack side
-, 0..99 0
Messk_ÜH-V X
Measuring circuit error in the suction gas temperature sensor for establishing the
superheat on the pack side
-, 0..99 0
Measuring circuit error for external to setpoint shift
-, 0..99 2
Messk.ext.HD-Sch X
Measuring circuit error for external HP setpoint shift in HR mode
-, 0..99 2
HD Not-AUS
The EMERGENCY OFF threshold for the high pressure has been exceeded and all
compressor stages have been shut down immediately.
-, 0..99 2
High LP
Message for low pressure too high, the limit value has been exceeded
-, 0..99 2