3-2-4 I-Wert X.XX
I-factor of the combined control for the ECO compressors
Example: for control error of 1 K with an I-Wert of 0.5, the I-component
changes with 0.05 V per cycle time (1 second) of the controller
Attention!
The set value is reduced by a factor of 10!
0.00..1.00
0.10
V/
K.s
3-2-4 MD-Offset X.Xb
Offset to the setpoint of the medium pressure valve regulation
0.5..2.5
1.0
bar
* The parameter is only displayed if the DIP switch S1 coding switch is set to ON
.
Associated connectors
Connector: Function
Terminals
Inputs
Digital
FC fault Z2
70/71
Relevant inputs for the Z2 safety chain
LP cutout Z2
72/73
Z2 compressor 1 HP/oil differential pressure switch
74/75
Z2 compressor 1 motor overload cutout
76/77
Z2 compressor 2 HP/oil differential pressure switch
92/93
Z2 compressor 2 motor overload cutout
96/97
Analogue
Z2 compressor suction gas temperature (Pt1000)
23/24
Outputs
Relays
Enable of the frequency converter for the Z2 compressor 1 15/16/18
Enable of the Z2 compressor 2
25/26/28
Analogue
Speed of the FC-controlled Z2 compressor (0..10 V)
63/64
5.8.2 Control by a VS 3015 C and a separate pack controller
Introduction
The ECO compressors are controlled via the VS 3015 C pack controller
and a separate
pack controller (e.g.
VS 3010) that receive an enable signal from the VS 3015 C pack controller. The VS 3015 C outputs the enable
signal at the relay output 10 (terminals 3/4).
Requirements
•
Second VS 3010 pack controller
•
The parameter "
ECO-Mode
" (menu 3-2-4) must be set to YES.
•
The parameter "
ECO-Compressor
" (menu 3-2-4) must be set to NO.